How to Read a Valve and Actuator Datasheet (Beginner’s Guide)

How-to-REad-a-Valve-Actuator-Datasheet

Picture a junior engineer on their second week. The boss drops two PDFs on the desk, one for a ball valve and one for an electric actuator, and says, “Check if these work together.” Both documents are full of abbreviations, small tables and numbers with units nobody explained.

If that sounds familiar, this guide is for you. We will go through a valve datasheet and an actuator datasheet line by line, in the order you would actually read them, and then show how to check that the two fit each other. You do not need a mechanical engineering degree. You do need the datasheet in front of you and a pen.

One note before we start. The numbers quoted below come from public datasheets and standards from various manufacturers, numbered at each point and listed under Sources. They show what a typical line looks like. They are not Cair product specifications, so always read the datasheet for the exact model you are buying.

What a datasheet is trying to tell you

Strip away the formatting and a datasheet answers four questions:

  1. Can the valve body survive the pressure and temperature of my line?
  2. Will it connect to my pipe?
  3. Will it shut off and flow the way my process needs?
  4. Can the actuator move it, reliably, in my site conditions?

Keep those four in mind and most of the page starts to make sense. Questions one to three belong to the valve datasheet. Question four is the actuator’s job.

Reading the valve datasheet

Size and pressure class

You will usually see a nominal size (for example 2 inch or DN50) next to a “Class” number. Under ASME B16.34, the standard pressure classes are 150, 300, 600, 900, 1500, 2500 and 4500 [1]. Write it as “Class 150”, not “150 pound”, because the class is a rating designation, not a weight or a single pressure [2].

Here is the part beginners miss. A class does not mean one fixed pressure. The allowable pressure falls as temperature rises. Milwaukee Valve’s chart for carbon steel A216 Gr. WCB [3] shows it clearly:

TemperatureClass 150 (psig)Class 300 (psig)
-20 to 100 °F285740
200 °F260680
300 °F230655
400 °F200635

So when a datasheet says “Class 150”, your next move is to find the pressure-temperature table for the body material and read the value at your design temperature, not at room temperature.

Do not assume you can swap one class for another either. Class 150 and Class 300 flanges have different bolt patterns [4], so a Class 300 valve will not bolt straight onto a Class 150 flange.

End connections

This line tells you how the valve joins the pipe: flanged, threaded (NPT), socket weld or butt weld. One manufacturer’s sheet, for example, lists socketweld, buttweld and NPT as standard [5]. For flanged valves, the datasheet should also name the flange standard, such as ASME B16.5, which appears in the API 6D recommended valve data sheet [6] quoted by engineers on a public forum.

Match this line with your piping spec before anything else. It is the cheapest mistake to catch and the most annoying one to find on site.

Cv (flow coefficient)

Cv is a number that describes how much fluid a valve passes. Apollo Valves defines it in its specification sheet [7] as the gallons of water per minute that flow with a 1 psig pressure difference across the valve. A bigger Cv means more flow for the same pressure drop.

Two practical cautions. First, Apollo notes its Cv factors come from flow testing and include the connection configuration, so the figure belongs to that valve as tested. Second, another manufacturer states that its Cv values are approximate and the factory should be contacted for exact figures [5]. If flow control matters in your process, treat Cv as a starting point and confirm it with the supplier.

Seat leakage class

This line answers “How tightly does it close?” You will often see something like “ANSI/FCI 70-2 Class IV” or “Class VI”. The standard defines six classes, I to VI [8]. Using the figures in the CFIHOS seat leakage list [9]:

  • Class II allows leakage of up to 0.5% of rated capacity
  • Class III allows up to 0.1%
  • Class IV allows up to 0.01%

Class VI is commonly called the soft seat classification [10], and it is counted in bubbles or millilitres per minute rather than a percentage.

One more thing worth knowing. FCI 70-2 was written for control valve seat leakage [11], while isolation valves are often tested to API 598 instead. And asking for Class VI everywhere is rarely wise: it forces soft seats, which may not survive high temperature or chemical attack [12], and it adds cost without helping.

Reading the actuator datasheet

Now flip to the actuator. The layout changes, but the logic is the same.

Torque: the number everything depends on

Torque is how much twisting force the actuator can deliver. Some datasheets give two figures. GF Piping Systems’ EA15 sheet, for example, lists a nominal torque of 10 Nm and a peak torque of 20 Nm [13]. Check which one the supplier uses when recommending the actuator for your valve.

On the valve side, the demand is not one number either. Sizing guides split it into breakaway torque (to unseat the ball or disc), running torque through mid-stroke, and seating torque [14]. Which one is highest depends on the valve: for resilient-seated butterfly valves, seating torque is often the highest demand point [14].

Then comes the safety factor. A trade-magazine guide on valve automation warns that a valve supplier sometimes includes a safety factor in the published torque, but you should never assume it [15]. One engineering knowledge base suggests applying 1.25 to 1.5 times the published breakaway torque [16], and Emerson’s sizing sheet works its examples with factors of 1.2 and 1.5 [17] depending on actuator type.

A quick made-up example, only to show the arithmetic: if the valve datasheet gives a breakaway torque of 40 Nm and your supplier recommends a factor of 1.25, the actuator should deliver at least 50 Nm (40 × 1.25).

Mounting interface (ISO 5211)

Torque is useless if the actuator does not physically bolt onto the valve. For quarter-turn valves, the mounting interface is usually written as “ISO 5211 F05” or “F03/F05”. The standard specifies flange dimensions, driving component dimensions and reference torque values [18] for attaching part-turn actuators to industrial valves, and a newer edition was published in February 2026 [19].

The F number is a size code. According to a supplier’s flange dimension table [20], F05 has a 50 mm pitch circle with M6 bolts, while F07 has a 70 mm pitch circle with M8 bolts. Different codes, different bolt holes, no fit. Read the valve’s top flange code and the actuator’s base code and make sure they match, or that the actuator lists both, like the Danfoss unit with an ISO 5211 F03/F05 interface [21].

Note that ISO 5211 covers part-turn actuators, and for control valves the attachment is subject to agreement between supplier and purchaser [22].

Voltage and current

Electric actuators come in specific supply voltages, and the same model can show up in several versions. Danfoss lists its MQT 010 F as separate items for 220 V [21] and 24 V [23], with a different maximum operating current for each (0.08 A and 0.75 A). Check the voltage against what your panel actually provides before you order.

Duty cycle

This tells you how hard you can work the actuator. Valbia’s manual says its actuator is designed for a nominal duty rating of 75% and asks you to verify duty suitability for your application [24]. Danfoss quotes S3 at 75% for AC and 85% for DC [21], and the GF Piping Systems EA15 sheet lists 40% [13]. That spread is exactly why this line deserves a look. A valve that opens and closes a few times a day is a very different job from one that modulates all shift.

Operating time

Usually written as seconds per 90 degrees. The GF Piping Systems sheet shows 5 s per 90° [13], and the Danfoss sheet shows 5.0 s for full travel [21]. Check it against what your process needs.

IP rating

“IP67” is easier than it looks. It comes from IEC 60529 [25]: the first digit covers solids, the second covers water. IP67 means dust-tight and protected against immersion between 15 cm and 1 m [25], while IP68 means protection against long-term immersion to a specified pressure.

A subtle point: for the water digit, a higher number does not automatically include the lower ones. Where you need both, a dual rating such as IP66/IP68 is specified [26]. If your actuator sits outdoors or gets washed down, look at that second digit carefully.

Fail-safe function

This line answers “What happens when the power goes?” Some actuators return to a set position. Asahi/America describes its failsafe version as one where capacitors power the unit to a predetermined position on power loss, with fail close as standard and fail open or fail as-is as options [27]. Not every actuator has this. Within one Danfoss range, one model lists the failsafe function as Yes [21] while another lists it as No [28]. A single letter in the model code can make that difference, so read that line, not just the title.

Extras worth scanning

Look for a manual override, position feedback and a heater. The GF Piping Systems sheet lists an integrated manual override, open/close feedback and an adjustable heater [13]. Also check the ambient temperature range. The Danfoss sheet above gives -40 °C to 45 °C [21], which might not suit a hot plant room.

A one-page checklist

CheckWhere to find itWhat to compare it with
Size and classValve datasheetPipe size and line design pressure
Pressure at temperatureP-T table for body materialYour maximum operating temperature
End connectionValve datasheetPiping spec and flange standard
CvValve datasheetFlow your process needs
Seat leakage classValve datasheetHow tight shut-off must be
Breakaway torqueValve datasheetActuator torque, after safety factor
Mounting codeValve top flange and actuator baseISO 5211 code on both
VoltageActuator datasheetYour power supply
Duty cycleActuator datasheetHow often the valve moves
IP ratingActuator datasheetIndoor or outdoor, washdown or not
Fail-safeActuator datasheetSafe position on power loss

Mistakes that cost time

Most datasheet problems come from small things: reading room-temperature pressure for a hot line, assuming the safety factor is already in the torque figure, ordering Class VI when Class IV was enough, or picking a 220 V actuator for a 24 V panel. Slow down on those lines and you avoid most of them.

Where to go from here

If you want to see how these lines look on real products, browse Cair’s range of electric actuators, including quarter turn, multi turn, linear and explosion proof models. On the valve side, there are motorized ball valves, motorized butterfly valves and motorized globe control valves, plus manual valves if you do not need automation.

Accessories also show up on datasheets, so it helps to know them: a limit switch box for position signals, a valve positioner for modulating control, a manual override for emergencies and a gear box when more torque is needed. You can also check the certificates page and the FAQ, or download the catalogue.

Still unsure whether a valve and actuator will match? Send the two datasheets, or just the valve size, pressure and voltage, through the inquiry form or the contact page and the Cair team can help you check the combination.

Quick questions

Does a higher pressure class always mean a better valve? No. It means a higher pressure rating, and a higher price. One buyer’s guide says Class 300 valves cost 50 to 100 percent more than Class 150 in the same material and size [4]. Pick the class your pressure and temperature need, not the biggest one available.

What does IP67 mean on an actuator? Dust-tight, and protected against immersion between 15 cm and 1 m deep, under IEC 60529 [25].

Do I need Class VI shut-off? Only if your process needs bubble-tight closure. Class IV allows 0.01% of rated capacity [9], which is enough for many services.

Sources

  • [1] ASME B16.34 overview, GlobalSpec. https://standards.globalspec.com/std/1194340/asme-b16-34
  • [2] Valve pressure classes, Wermac. https://www.wermac.org/valves/valves_B16_34.html
  • [3] Pressure/temperature chart, Milwaukee Valve. https://www.milwaukeevalve.com/wp-content/uploads/tov-pressure-temp-charts_v4.pdf
  • [4] Class 150 vs Class 300, Project Materials. https://blog.projectmaterials.com/quick-answers/valves/class-150-vs-class-300-valve/
  • [5] ValvTechnologies V1-1 data sheet. https://www.valv.com/ebrochures/attachment/300_v1-1-data-sheet_april-2018/
  • [6] Valve datasheet preparation thread, CR4/GlobalSpec. https://cr4.globalspec.com/thread/19504/Valve-Datasheet-Preparation
  • [7] Apollo Valves specification sheet. https://www.cooneybrothers.com/userfiles/ad/documents/Apollo_7330801_Specification_Sheet.pdf
  • [8] Control valve leakage classifications, ElectricalVolt. https://www.electricalvolt.com/control-valves-leakage-classifications
  • [9] Seat leakage class, CFIHOS. https://cfihos.kraken.im/picklists/seat-leakage-class
  • [10] ANSI leakage classes, SVF. https://svf.net/wp-content/uploads/2021/10/ANSI-Leakage-Classes.pdf
  • [11] ANSI/FCI 70-2-2006. https://cncontrolvalve.com/wp-content/uploads/2021/03/AMERICAN-NATIONAL-STANDARD-Control-Valve-Seat-Leakage.pdf
  • [12] Valve leakage class, Project Materials. https://blog.projectmaterials.com/quick-answers/valves/valve-leakage-class/
  • [13] GF Piping Systems EA15 data sheet. https://s3.amazonaws.com/zcom-media/sites/a0i0L00000VJ0SJQA1/media/mediamanager/gfps-us-1334-datasheet-EA15-Data-Sheet-en.pdf
  • [14] Valve actuator sizing, Fabrico. https://www.fabrico.io/ro/blog/valve-actuator-sizing/
  • [15] How to automate butterfly and ball valves, Water & Wastes Digest. https://www.wwdmag.com/flow-metering/how-automate-butterfly-ball-valves
  • [16] Valve torque calculation methods, Industrial Monitor Direct. https://industrialmonitordirect.com/blogs/knowledgebase/valve-torque-calculation-methods-for-actuator-selection
  • [17] Sizing of rack and pinion actuators, Emerson. https://emerson.com/documents/automation/product-data-sheet-sizing-of-rack-pinion-actuators-bettis-en-1568566.pdf
  • [18] ISO 5211, Industrial valves: Part-turn actuator attachments, BSI Knowledge. https://knowledge.bsigroup.com/products/industrial-valves-part-turn-actuator-attachments-3
  • [19] ISO 5211:2026, Standards Council of Canada. https://scc-ccn.ca/standardsdb/standards/8190493
  • [20] ISO 5211 flange dimensions, CN Control Valve. https://cncontrolvalve.com/iso-5211-mounted-flange-dimensions/
  • [21] Danfoss MQT 010 F actuator, 220 V. https://designcenter.danfoss.com/products/p/009L2186
  • [22] ISO 5211:2023, Standards New Zealand. https://www.standards.govt.nz/shop/ISO-52112023
  • [23] Danfoss MQT 010 F actuator, 24 V. https://designcenter.danfoss.com/products/p/009L2187
  • [24] Valbia electric actuator manual. https://cdn.shopify.com/s/files/1/0736/5004/5228/files/IOM-VB015M_ON-OFF.pdf
  • [25] IP67 explained, Zenitel. https://www.zenitel.com/technology/environment/ip67
  • [26] IP67 vs IP68, Index Enclosures. https://indexenclosures.com/ip67-vs-ip68/
  • [27] Series 19 failsafe actuator, Asahi/America. https://www.asahi-america.com/valves-actuation/actuators/electric/series-19-smart-actuators/series-19-failsafe/series-19-fail-safe-actuator-only/
  • [28] Danfoss MQT 010 N actuator. https://designcenter.danfoss.com/nl-nl/products/p/009L2189

Leave a Reply

Your email address will not be published. Required fields are marked *